released, and in 2 out of 2 mode both the CRs should be high to release trip signal. If
any one of the channel error signals is high in 2 out of 2 mode, then logic automatically
switches to 1 out of 2 mode after a time delay of 200 ms. After switching to 1/2 mode
under channel error condition and if channel error gets cleared the mode will switch
back only after a time delay of 200 ms.
If the input channel error signal is high then the respective carrier receive signal will be
blocked.
The complete function can be blocked by setting the BLOCK input high.
13.8.5.3 Function block
ANSI09000766-1-en.vsd
LCCRPTRC (94)
BLOCK
LOCTR
LOCTR_A
LOCTR_B
LOCTR_C
CHERR1
CHERR2
CR!
CR2
TRIP
TR_A
TR_B
TR_C
ANSI09000766 V1 EN
Figure 420: LCCRPTRC (94) function block
13.8.5.4 Input and output signals
Table 463: LCCRPTRC (94) Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
LOCTR BOOLEAN 0 Local common trip signal coming from DTT
LOCTR_A BOOLEAN 0 Local trip signal for phase A coming from DTT
LOCTR_B BOOLEAN 0 Local trip signal for phase B coming from DTT
LOCTR_C BOOLEAN 0 Local trip signal for phase C coming from DTT
CHERR1 BOOLEAN 0 Channel error indication flag for carrier receive 1
CHERR2 BOOLEAN 0 Channel error indication flag for carrier receive 2
CR! BOOLEAN 0 Carrier receive 1
CR2 BOOLEAN 0 Carrier receive 2
1MRK505222-UUS C Section 13
Scheme communication
843
Technical reference manual