16.2.3 Function block
IEC07000120-2-en.vsd
ETPMMTR
P
Q
STACC
RSTACC
RSTDMD
ACCST
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC07000120 V2 EN
Figure 484: ETPMMTR function block
16.2.4 Input and output signals
Table 607: ETPMMTR Input signals
Name
Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STACC BOOLEAN 0 Start to accumulate energy values
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading
Table 608: ETPMMTR Output signals
Name
Type Description
ACCST BOOLEAN Start of accumulating energy values.
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
ERFPULSE BOOLEAN Accumulated forward reactive energy pulse
ERRPULSE BOOLEAN Accumulated reverse reactive energy pulse
EAFALM BOOLEAN Alarm for active forward energy exceed limit in set
interval
EARALM BOOLEAN Alarm for active reverse energy exceed limit in set
interval
Table continues on next page
1MRK505222-UUS C Section 16
Metering
989
Technical reference manual