EasyManua.ls Logo

ABB Relion 670 series - Reset-set with memory function block RSMEMORY

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 517: SRMEMORY Output signals
Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
Table 518: SRMEMORY Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Disabled
Enabled
- - Enabled Operating mode of the memory function
14.3.10 Reset-set with memory function block RSMEMORY
The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory
that can reset or set an output from two inputs respectively. Each RSMEMORY
function block has two outputs, where one is inverted. The memory setting controls if
the flip-flop after a power interruption will return the state it had before or if it will be
reset. For a Reset-Set flip-flop, RESET input has higher priority over SET input.
Table 519: Truth table for RSMEMORY function block
RESET
SET OUT NOUT
0 0 Last
value
Inverted last
value
0 1 1 0
1 0 0 1
1 1 0 1
RSMEMORY
SET
RESET
OUT
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Figure 444: RSMEMORY function block
Table 520: RSMEMORY Input signals
Name
Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset