17.9.6 Setting parameters
Table 675: MULTICMDRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.050 - 200.000 s 0.001 11.000 Maximum cycle time between receptions of
input data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum cycle time between receptions of
input data
Mode Steady
Pulsed
- - Steady Mode for output signals
tPulseTime 0.000 - 60.000 s 0.001 0.200 Pulse length for multi command outputs
Table 676: MULTICMDSND Non group settings (basic)
Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.000 - 200.000 s 0.001 5.000 Maximum time interval between transmission
of output data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum time interval between transmission
of output data