4.3.4 Output signals
Table 20: TIMEERR Output signals
Name Type Description
TSYNCERR BOOLEAN Time synchronization error
RTCERR BOOLEAN Real time clock error
4.3.5 Setting parameters
Path in the local HMI is located under Main menu/Setting/Time
Path in PCM600 is located under Main menu/Settings/Time/Synchronization
Table 21: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Disabled
SPA
LON
SNTP
DNP
- - Disabled Coarse time synchronization source
FineSyncSource Disabled
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Disabled Fine time synchronization source
SyncMaster Disabled
SNTP-Server
- - Disabled Activate IED as synchronization master
TimeAdjustRate Slow
Fast
- - Fast Adjust rate for time synchronization
HWSyncSrc Disabled
GPS
IRIG-B
PPS
- - Disabled Hardware time synchronization source
AppSynch NoSynch
Synch
- - NoSynch Time synchronization mode for application
SyncAccLevel Class T5 (1us)
Class T4 (4us)
Unspecified
- - Unspecified Wanted time synchronization accuracy