17.2.5.3 Input and output signals
Table 615: MVGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analogue input value
Table 616: MVGGIO Output signals
Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range
17.2.5.4 Setting parameters
Table 617: MVGGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
MV hhLim -10000000000.000
- 10000000000.000
- 0.001 90.000 High High limit
MV hLim -10000000000.000
- 10000000000.000
- 0.001 80.000 High limit
MV lLim -10000000000.000
- 10000000000.000
- 0.001 -80.000 Low limit
MV llLim -10000000000.000
- 10000000000.000
- 0.001 -90.000 Low Low limit
MV min -10000000000.000
- 10000000000.000
- 0.001 -100.000 Minimum value
MV max -10000000000.000
- 10000000000.000
- 0.001 100.000 Maximum value
MV dbType Cyclic
Dead band
Int deadband
- - Dead band Reporting type
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
17.2.6 IEC 61850-8-1 redundant station bus communication