IEC04000378-3-en.vsd
TIMER
INPUT ON
OFF
IEC04000378 V2 EN
Figure 439: TIMER function block
Table 505: TIMER Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input to timer
Table 506: TIMER Output signals
Name Type Description
ON BOOLEAN Output from timer , pickup delay
OFF BOOLEAN Output from timer, dropout delay
Table 507: TIMER Non group settings (basic)
Name Values (Range) Unit Step Default Description
T 0.000 - 90000.000 s 0.001 0.000 Time delay of function
14.3.6 Pulse timer function block PULSETIMER
The pulse (PULSETIMER) function can be used, for example, for pulse extensions or
limiting of operation of outputs. The pulse timer TP has a settable length.
IEC04000407-2-en.vsd
PULSETIMER
INPUT
T
OUT
IEC04000407 V2 EN
Figure 440: PULSETIMER function block
Table 508: PULSETIMER Input signals
Name
Type Default Description
INPUT BOOLEAN 0 Input to pulse timer
Table 509: PULSETIMER Output signals
Name
Type Description
OUT BOOLEAN Output from pulse timer
1MRK505222-UUS C Section 14
Logic
875
Technical reference manual