Sometimes, the mechanical power from a prime mover may decrease so much that it
does not cover bearing losses and ventilation losses. Then, the synchronous generator
becomes a synchronous motor and starts to take electric power from the rest of the
power system. This operating state, where individual synchronous machines operate as
motors, implies no risk for the machine itself. If the generator under consideration is
very large and if it consumes lots of electric power, it may be desirable to disconnect it
to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state.
The task of the reverse power protection is to protect the turbine and not to protect the
generator itself.
Figure 
242 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a higher
margin and should provide better dependability. On the other hand, the risk for
unwanted operation immediately after synchronization may be higher. One should set
the underpower IED to trip if the active power from the generator is less than about
2%. One should set the overpower IED to trip if the power flow from the network to
the generator is higher than 1%.
When IED with a metering class input CTs is used pickup can be set to more sensitive
value (e.g.0,5% or even to 0,2%).
Underpower IED
Overpower IED
Q Q
P P
Operating point 
without 
turbine torque
Margin Margin
Operate
Line
Operate
Line
Operating point 
without 
turbine torque
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Figure 242: Reverse power protection with underpower IED and overpower IED
7.12.2  Principle of operation
A simplified scheme showing the principle of the power protection function is shown
in figure 
243. The function has two stages with individual settings.
1MRK505222-UUS C Section 7
Current protection
479
Technical reference manual