Table 12: LEDGEN Output signals
Name Type Description
NEWIND BOOLEAN A new signal on any of the indication inputs occurs
ACK BOOLEAN A pulse is provided when the LEDs are acknowledged
3.5.4.5  Setting parameters
Table 13: LEDGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation mode for the LED function
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of a
disturbance
SeqTypeLED1 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 1
SeqTypeLED2 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 2
SeqTypeLED3 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 3
SeqTypeLED4 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 4
SeqTypeLED5 Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
- - Follow-S Sequence type for LED 5
Table continues on next page
Section 3 1MRK505222-UUS C
Local HMI
72
Technical reference manual