15.2.6 Setting parameters
Table 572: CNTGGIO Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
15.2.7 Technical data
Table 573: CNTGGIO technical data
Function Range or value Accuracy
Counter value 0-100000 -
Max. count up speed 10 pulses/s (50% duty cycle) -
15.3 Event function EVENT
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function EVENT
S00946 V1 EN
-
15.3.1 Introduction
When using a Substation Automation system with LON or SPA communication, time-
tagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT). The event function block is used for remote communication.
Analog and double indication values are also transferred through EVENT function.
15.3.2 Principle of operation
The main purpose of the event function (EVENT) is to generate events when the state
or value of any of the connected input signals is in a state, or is undergoing a state
transition, for which event generation is enabled.
Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a
name from the Application Configuration tool. The inputs are normally used to create
single events, but are also intended for double indication events.
1MRK505222-UUS C Section 15
Monitoring
931
Technical reference manual