Table 583: LMBRFLO Non group settings (basic)
Name Values (Range) Unit Step Default Description
DrepChNoI_A 1 - 30 Ch 1 1 Recorder Input number recording phase
current, IA
DrepChNoI_B 1 - 30 Ch 1 2 Recorder Input number recording phase
current, IB
DrepChNoI_C 1 - 30 Ch 1 3 Recorder Input number recording phase
current, IC
DrepChNoIN 0 - 30 Ch 1 4 Recorder input number recording residual
current, IN
DrepChNoIP 0 - 30 Ch 1 0 Recorder input number recording 3I0 on
parallel line
DrepChNoV_A 1 - 30 Ch 1 5 Recorder Input number recording phase
voltage, VA
DrepChNoV_B 1 - 30 Ch 1 6 Recorder Input number recording phase
voltage, VB
DrepChNoV_C 1 - 30 Ch 1 7 Recorder Input number recording phase
voltage, VC
15.5.6  Technical data
Table 584: LMBRFLO technical data
Function
Value or range Accuracy
Reactive and resistive reach (0.001-1500.000) Ω/phase ± 2.0% static accuracy
± 2.0% degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Phase selection According to input signals -
Maximum number of fault
locations
100 -
15.6  Measured value expander block RANGE_XP
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block RANGE_XP - -
1MRK505222-UUS C Section 15
Monitoring
947