4.6.3 Function block
TESTMODE
INPUT ACTIVE
OUTPUT
SETTING
NOEVENT
IEC09000219-1.vsd
IEC09000219 V1 EN
Figure 34: TESTMODE function block
4.6.4 Input and output signals
Table 35: TESTMODE Input signals
Name Type Default Description
INPUT BOOLEAN 0 Sets terminal in test mode when active
Table 36: TESTMODE Output signals
Name Type Description
ACTIVE BOOLEAN IED in test mode when active
OUTPUT BOOLEAN Test input is active
SETTING BOOLEAN Test mode setting is (Enabled) or not (Disabled)
NOEVENT BOOLEAN Event disabled during testmode
4.6.5 Setting parameters
Table 37: TESTMODE Non group settings (basic)
Name
Values (Range) Unit Step Default Description
TestMode Disabled
Enabled
- - Disabled Test mode in operation (Enabled) or not
(Disabled)
EventDisable Disabled
Enabled
- - Disabled Event disable during testmode
CmdTestBit Disabled
Enabled
- - Disabled Command bit for test required or not during
testmode
Section 4 1MRK505222-UUS C
Basic IED functions
102
Technical reference manual