12.8.5 Setting parameters
Table 391: SPC8GGIO Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
Latched1 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Output1 Pulse Time
Latched2 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Output2 Pulse Time
Latched3 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Output3 Pulse Time
Latched4 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Output4 Pulse Time
Latched5 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Output5 Pulse Time
Latched6 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Output6 Pulse Time
Latched7 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 7
tPulse7 0.01 - 6000.00 s 0.01 0.10 Output7 Pulse Time
Latched8 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Output8 pulse time
12.9 AutomationBits, command function for DNP3.0
AUTOBITS
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AutomationBits, command function for
DNP3
AUTOBITS - -
Section 12 1MRK505222-UUS C
Control
766