7.12.5 Setting parameters
Table 243: GOPPDOP (32) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
OpMode1 Disabled
OverPower
- - OverPower Operation mode 1
Power1 0.0 - 500.0 %SB 0.1 120.0 Power setting for stage 1 in % of Sbase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 1
TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1
DropDelay1 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 1
OpMode2 Disabled
OverPower
- - OverPower Operation mode 2
Power2 0.0 - 500.0 %SB 0.1 120.0 Power setting for stage 2 in % of Sbase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 2
TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2
DropDelay2 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 2
Table 244: GOPPDOP (32) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 1 in % of Sbase
Hysteresis2 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 2 in % of Sbase
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of
In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30%
of In
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%
of In
VMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 5% of
Vn
VMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 30%
of Vn
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%
of Vn
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
1MRK505222-UUS C Section 7
Current protection
485
Technical reference manual