Quantity Rated value Nominal range
Burden < 150 mVA at I
n
 = 5 A
< 20 mVA at I
n
 = 1 A
 
Ac voltage V
n
 = 120 V 0.5–288 V
Operative range (0–340) V  
Permissive overload 420 V cont.
450 V 10 s
 
Burden < 20 mVA at 110 V  
Frequency f
n
 = 60/50 Hz ± 5%
*)
 max. 350 A for 1 s when COMBITEST test switch is included.
Table 693: TRM - Energizing quantities, rated values and limits for measuring transformer modules
Quantity Rated value Nominal range
Current I
n
 = 1 or 5 A (0-1.8) × I
n 
at I
n
 = 1 A
(0-1.6) × I
n 
at I
n
 = 5 A
Permissive overload 1.1 × I
n 
 cont.
1.8 × I
n 
 for 30 min at I
n
 = 1 A
1.6 × I
n 
 for 30 min at I
n
 = 5 A
 
Burden < 350 mVA at I
n
 = 5 A
< 200 mVA at I
n
 = 1 A
 
Ac voltage V
n
 = 120 V 0.5–288 V
Operative range (0–340) V  
Permissive overload 420 V cont.
450 V 10 s
 
Burden < 20 mVA at 110 V  
Frequency f
n
 = 60/50 Hz ± 5%
19.2.8  Analog digital conversion module, with time synchronization
(ADM)
19.2.8.1  Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC slot.
The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards according
to table 694. The OEM card should always be mounted on the ADM board. The UBM
connects the ADM to the transformer input module (TRM).