11.2.5 Setting parameters
Table 313: SDDRFUF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
IBase 1 - 99999 A 1 3000 Base current
VBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage
OpModeSel Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
- - V0I0 Operating mode selection
3V0PU 1 - 100 %VB 1 30 Pickup of residual overvoltage element in %
of VBase
3I0PU 1 - 100 %IB 1 10 Pickup of residual undercurrent element in %
of IBase
3V2PU 1 - 100 %VB 1 30 Pickup of negative sequence overvoltage
element in % of VBase
3I2PU 1 - 100 %IB 1 10 Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI Disabled
Enabled
- - Disabled Operation of change based function Disable/
Enable
DVPU 1 - 100 %VB 1 60 Pickup of change in phase voltage in % of
VBase
DIPU 1 - 100 %IB 1 15 Pickup of change in phase current in % of
IBase
VPPU 1 - 100 %VB 1 70 Pickup of phase voltage in % of VBase
IPPU 1 - 100 %IB 1 10 Pickup of phase current in % of IBase
SealIn Disabled
Enabled
- - Enabled Seal in functionality Disable/Enable
VSealInPU 1 - 100 %VB 1 70 Pickup of seal-in phase voltage in % of VBase
IDLDPU 1 - 100 %IB 1 5 Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU 1 - 100 %VB 1 60 Pickup for phase voltage detection in % of
VBase for dead line detection