Name Type Default Description
QB61_CL BOOLEAN 0 6189 is in closed position
QB62_OP BOOLEAN 0 6289 is in open position
QB62_CL BOOLEAN 0 6289 is in closed position
QC1_OP BOOLEAN 0 189G is in open position
QC1_CL BOOLEAN 0 189G is in closed position
QC2_OP BOOLEAN 0 289G is in open position
QC2_CL BOOLEAN 0 289G is in closed position
1QC3_OP BOOLEAN 0 1389G on line 1 is in open position
1QC3_CL BOOLEAN 0 1389G on line 1 is in closed position
2QC3_OP BOOLEAN 0 2389G on line 2 is in open position
2QC3_CL BOOLEAN 0 2389G on line 2 is in closed position
QB61_EX1 BOOLEAN 0 External condition for apparatus 6189
QB61_EX2 BOOLEAN 0 External condition for apparatus 6189
QB62_EX1 BOOLEAN 0 External condition for apparatus 6289
QB62_EX2 BOOLEAN 0 External condition for apparatus 6289
Table 368: BH_CONN (3) Output signals
Name
Type Description
QA1CLREL BOOLEAN Closing of 152 is allowed
QA1CLITL BOOLEAN Closing of 152 is not allowed
QB61REL BOOLEAN Switching of 6189 is allowed
QB61ITL BOOLEAN Switching of 6189 is not allowed
QB62REL BOOLEAN Switching of 6289 is allowed
QB62ITL BOOLEAN Switching of 6289 is not allowed
QC1REL BOOLEAN Switching of 189G is allowed
QC1ITL BOOLEAN Switching of 189G is not allowed
QC2REL BOOLEAN Switching of 289G is allowed
QC2ITL BOOLEAN Switching of 289G is not allowed