The binary signals connected to BxRBDR are reported by polling. The function blocks
include function type and information number.
15.12.3 Function block
The Disturbance recorder has no function block of it’s own. It is included in the
DRPRDRE, AxRADR and BxRBDR block.
15.12.4 Input and output signals
For signals see section, in Disturbance report,
"Input and output signals".
15.12.5 Setting parameters
For Setting parameters see section "Disturbance report DRPRDRE".
15.12.6 Technical data
Table 602: technical data
Function
Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz