EasyManua.ls Logo

ABB Relion 670 series - Input and output signals

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4.4 Input and output signals
Table 118: ZMHPDIS (21) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Connection for current sample signals
V3P GROUP
SIGNAL
- Connection for voltage sample signals
CURR_INP GROUP
SIGNAL
- Connection for current signals
VOLT_INP GROUP
SIGNAL
- Connection for voltage signals
POL_VOLT GROUP
SIGNAL
- Connection for polarizing voltage
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block due to fuse failure
BLKZMTD BOOLEAN 0 Block signal for blocking of time domaine function
BLKHSIR BOOLEAN 0 Blocks time domain function at high SIR
BLKTRIP BOOLEAN 0 Blocks all operate output signals
BLKPG BOOLEAN 0 Blocks phase-to-ground operation
BLKPP BOOLEAN 0 Blocks phase-to-phase operation
DIRCND INTEGER 0 External directional condition
PHSEL INTEGER 0 Faulted phase loop selection enable from phase
selector
LDCND INTEGER 0 External load condition (loop enabler)
Table 119: ZMHPDIS (21) Output signals
Name
Type Description
TRIP BOOLEAN Trip General
TR_A BOOLEAN Trip phase A
TR_B BOOLEAN Trip phase B
TR_C BOOLEAN Trip phase C
TRPG BOOLEAN Trip phase-to-ground
TRPP BOOLEAN Trip phase-to-phase
PICKUP BOOLEAN Pickup General
PU_A BOOLEAN Pickup phase A
PU_B BOOLEAN Pickup phase B
PU_C BOOLEAN Pickup phase C
PHG_FLT BOOLEAN Pickup phase-to-ground
PHPH_FLT BOOLEAN Pickup phase-to-phase
Section 6 1MRK505222-UUS C
Impedance protection
258
Technical reference manual