19.2.7  Transformer input module (TRM)
19.2.7.1  Introduction
The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The module
has twelve inputs in different combinations of currents and voltage inputs.
Alternative connectors of Ring lug or Compression type can be ordered.
19.2.7.2  Design
The transformer module has 12 input transformers. There are several versions of the
module, each with a different combination of voltage and current input transformers.
Basic versions:
• 6 current channels and 6 voltage channels
• 7 current channels and 5 voltage channels
• 9 current channels and 3 voltage channels
• 12 current channels
The rated values and channel type, measurement or protection, of the current inputs are
selected at order.
Transformer input module for measuring should not be used with
current transformers intended for protection purposes, due to
limitations in overload characteristics.
The TRM is connected to the ADM and NUM via the UBM.
For configuration of the input and output signals, refer to section 
 "Signal matrix for
analog inputs SMAI".
19.2.7.3  Technical data
Table 692: TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Rated value Nominal range
Current I
n
 = 1 or 5 A (0.2-40) × I
n
Operative range (0-100) x I
n
 
Permissive overload 4 × I
n
 cont.
100 × I
n
 for 1 s 
*)
 
Table continues on next page
1MRK505222-UUS C Section 19
IED hardware
1095
Technical reference manual