7.11.3 Function block
ANSI07000027-2-en.vsd
GUPPDUP (37)
I3P*
V3P*
BLOCK
BLOCK1
BLOCK2
TRIP
TRIP1
TRIP2
PICKUP
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI07000027 V2 EN
Figure 241: GUPPDUP (37) function block
7.11.4 Input and output signals
Table 234: GUPPDUP (37) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Current group connection
V3P GROUP
SIGNAL
- Voltage group connection
BLOCK BOOLEAN 0 Block of function
BLOCK1 BOOLEAN 0 Block of stage 1
BLOCK2 BOOLEAN 0 Block of stage 2
Table 235: GUPPDUP (37) Output signals
Name
Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
PICKUP BOOLEAN Common pickup
PICKUP1 BOOLEAN Pickup of stage 1
PICKUP2 BOOLEAN Pickup of stage 2
P REAL Active Power in MW
PPERCENT REAL Active power in % of SBASE
Q REAL Reactive power in Mvar
QPERCENT REAL Reactive power in % of SBASE
Section 7 1MRK505222-UUS C
Current protection
476
Technical reference manual