Name Type Default Description
INPUT18 BOOLEAN 0 Binary input 18
INPUT19 BOOLEAN 0 Binary input 19
INPUT20 BOOLEAN 0 Binary input 20
INPUT21 BOOLEAN 0 Binary input 21
INPUT22 BOOLEAN 0 Binary input 22
INPUT23 BOOLEAN 0 Binary input 23
INPUT24 BOOLEAN 0 Binary input 24
INPUT25 BOOLEAN 0 Binary input 25
INPUT26 BOOLEAN 0 Binary input 26
INPUT27 BOOLEAN 0 Binary input 27
INPUT28 BOOLEAN 0 Binary input 28
INPUT29 BOOLEAN 0 Binary input 29
INPUT30 BOOLEAN 0 Binary input 30
INPUT31 BOOLEAN 0 Binary input 31
INPUT32 BOOLEAN 0 Binary input 32
Table 497: TMAGGIO Output signals
Name
Type Description
OUTPUT1 BOOLEAN OR function betweeen inputs 1 to 16
OUTPUT2 BOOLEAN OR function between inputs 17 to 32
OUTPUT3 BOOLEAN OR function between inputs 1 to 32
14.2.5 Setting parameters
Table 498: TMAGGIO Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Operation Disable / Enable
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
ModeOutput1 Steady
Pulsed
- - Steady Mode for output ,1 steady or pulsed
ModeOutput2 Steady
Pulsed
- - Steady Mode for output 2, steady or pulsed
ModeOutput3 Steady
Pulsed
- - Steady Mode for output 3, steady or pulsed
1MRK505222-UUS C Section 14
Logic
871
Technical reference manual