8.6.6  Technical data
Table 284: LOVPTUV (27) technical data
Function Range or value Accuracy
Operate voltage (0–100)% of VBase ± 0.5% of V
n
Pulse timer (0.050–60.000) s ± 0.5% ± 10 ms
Timers (0.000–60.000) s ± 0.5% ± 10 ms
1MRK505222-UUS C Section 8
Voltage protection
549
Technical reference manual