17.9.3 Design
17.9.3.1 General
The output signals can be of the types Disabled, Steady, or Pulse. The setting is done
on the MODE settings, common for the whole block, from PCM600.
0 = Disabled sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values sent
from the station level.
2 = Pulse gives a pulse with one execution cycle duration, if a value sent from the
station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer than
the execution cycle time for the command function block.
17.9.4 Function block
IEC06000007-2-en.vsd
MULTICMDRCV
BLOCK ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID
IEC06000007 V2 EN
Figure 499: MULTICMDRCV function block
1MRK505222-UUS C Section 17
Station communication
1065
Technical reference manual