Name Values (Range) Unit Step Default Description
FrRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
IBase 1 - 99999 A 1 3000 Base setting for current values in A
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage value in kV
SBase 0.05 - 200000.00 MVA 0.05 2080.00 Base setting for power values in MVA
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - A, B, C Selection of measured current and voltage
PowMagFact 0.000 - 6.000 - 0.001 1.000 Magnitude factor to scale power calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift between
measured I & V
k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power
measurement, V and I
Table 553: CVMMXN Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
SDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
SZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
PDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
PZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
QDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table continues on next page
Section 15 1MRK505222-UUS C
Monitoring
914
Technical reference manual