EasyManua.ls Logo

ABB Relion 670 series - Page 1199

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 733: Inverse time characteristics for residual overvoltage protection
Function Range or value Accuracy
Type A curve:
=
-
æ ö
ç ÷
è ø
t
td
V VPickup
VPickup
EQUATION1661 V1 EN
V = V
measured
td = (0.05-1.10) in steps
of 0.01
5% +40 ms
Type B curve:
=
×
-
× - -
æ ö
ç ÷
è ø
2.0
480
32 0.5 0.035
t
td
V VPickup
VPickup
EQUATION1662 V1 EN
td = (0.05-1.10) in steps
of 0.01
Type C curve:
=
×
-
× - -
æ ö
ç ÷
è ø
3.0
480
32 0.5 0.035
t
td
V VPickup
VPickup
EQUATION1663 V1 EN
td = (0.05-1.10) in steps
of 0.01
Programmable curve:
×
= +
-
× -
æ ö
ç ÷
è ø
P
td A
t D
V VPickup
B C
VPickup
EQUATION1664 V1 EN
td = (0.05-1.10) in steps
of 0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001
1MRK505222-UUS C Section 22
Inverse time characteristics
1193
Technical reference manual

Table of Contents