EasyManua.ls Logo

ABB Relion 670 series - Page 330

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 153: ZMRAPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Operation Disable / Enable
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
VBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Disabled
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1PP 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach Ph-Ph
R1PP 0.01 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFPP 0.10 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
X1PG 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach Ph-G
R1PG 0.01 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-G
X0PG 0.10 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-G
R0PG 0.01 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone characteristic
angle, Ph-G
RFPG 0.10 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-G
OperationPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Phase loops
Timer tPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPG Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Ground loops
Timer tPG Disabled
Enabled
- - Enabled Operation mode Disable/ Enable of Zone
timer, Ph-G
tPG 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-G
IMinPUPP 10 - 1000 %IB 1 20 Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
IMinPUPG 10 - 1000 %IB 1 20 Minimum pickup phase current for Phase-to-
ground loops
Table 154: ZDRDIR (21D) Group settings (basic)
Name
Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base setting for current level
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
IMinPUPP 5 - 30 %IB 1 10 Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Table continues on next page
Section 6 1MRK505222-UUS C
Impedance protection
324
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals