Info. no. Message Supported
91 Over current trip I>> Yes
92 Ground fault trip IN> Yes
93 Ground fault trip IN>> Yes
Autorecloser indications in monitor direction, I103AR
Indication block for autorecloser in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Info. no. Message Supported
16 Autorecloser active Yes
17 Teleprotection active No
18 Protection active No
128 CB on by Autorecloser Yes
129 CB ‘on’ by long-time AR No
130 Autorecloser blocked Yes
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.
Measurands in public range, I103Meas
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no.
Message Supported
148 I_A Yes
144, 145,
148
I_B Yes
148 I_C Yes
147 IN, Neutral current Yes
Table continues on next page
Section 17 1MRK505222-UUS C
Station communication
1042
Technical reference manual