Table 644: I103SUPERV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm
Table 645: I103EF Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
51_EFFW BOOLEAN 0 Information number 51, ground-fault forward
52_EFREV BOOLEAN 0 Information number 52, ground-fault reverse
Table 646: I103FLTDIS Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
64_PU_A BOOLEAN 0 Information number 64, start phase A
65_PU_B BOOLEAN 0 Information number 65, start phase B
66_PU_C BOOLEAN 0 Information number 66, start phase C
67_STIN BOOLEAN 0 Information number 67, start residual current IN
84_STGEN BOOLEAN 0 Information number 84, start general
69_TR_A BOOLEAN 0 Information number 69, trip phase A
70_TR_B BOOLEAN 0 Information number 70, trip phase B
71_TR_C BOOLEAN 0 Information number 71, trip phase C
68_TRGEN BOOLEAN 0 Information number 68, trip general
74_FW BOOLEAN 0 Information number 74, forward/line
75_REV BOOLEAN 0 Information number 75, reverse/bus
78_ZONE1 BOOLEAN 0 Information number 78, zone 1
79_ZONE2 BOOLEAN 0 Information number 79, zone 2
80_ZONE3 BOOLEAN 0 Information number 79, zone 3
81_ZONE4 BOOLEAN 0 Information number 79, zone 4
82_ZONE5 BOOLEAN 0 Information number 79, zone 5
76_TRANS BOOLEAN 0 Information number 76, signal transmitted
Table continues on next page
Section 17 1MRK505222-UUS C
Station communication
1052