EasyManua.ls Logo

ABB Relion 670 series - Page 197

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Description
PU_A BOOLEAN Pickup signal from phase A
PU_B BOOLEAN Pickup signal from phase B
PU_C BOOLEAN Pickup signal from phase C
PHPUND BOOLEAN Non-directional pickup, issued from any selected
phase or loop
Table 95: ZMQAPDIS (21) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Group signal for current input
V3P GROUP
SIGNAL
- Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
LOVBZ BOOLEAN 0 Blocks all output for LOV (or fuse failure) condition
BLKTR BOOLEAN 0 Blocks all trip outputs
PHSEL INTEGER 0 Faulted phase loop selection enable from phase
selector
DIRCND INTEGER 0 External directional condition
Table 96: ZMQAPDIS (21) Output signals
Name
Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TR_A BOOLEAN Trip signal from phase A
TR_B BOOLEAN Trip signal from phase B
TR_C BOOLEAN Trip signal from phase C
PICKUP BOOLEAN General Pickup, issued from any phase or loop
PU_A BOOLEAN Pickup signal from phase A
PU_B BOOLEAN Pickup signal from phase B
PU_C BOOLEAN Pickup signal from phase C
PHPUND BOOLEAN Non-directional pickup, issued from any selected
phase or loop
Table 97: ZDRDIR (21D) Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- group connection for current abs 2
V3P GROUP
SIGNAL
- group connection for voltage abs 2
1MRK505222-UUS C Section 6
Impedance protection
191
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals