EasyManua.ls Logo

ABB Relion 670 series - Page 221

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPG Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Ground loops
X1FwPG 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-G,
forward
R1PG 0.01 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-G
X0PG 0.10 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach, Ph-G
R0PG 0.01 - 3000.00 ohm/p 0.01 47.00 Zero seq. resistance for zone characteristic
angle, Ph-G
RFltFwdPG 0.10 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-G, forward
X1RvPG 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-G,
reverse
RFltRevPG 0.10 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach, Ph-G, reverse
Timer tPG Disabled
Enabled
- - Enabled Operation mode Disable/ Enable of Zone
timer, Ph-G
tPG 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-G
IMinPUPP 10 - 1000 %IB 1 20 Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
IMinPUPG 10 - 1000 %IB 1 20 Minimum pickup phase current for Phase-to-
ground loops
IMinOpIR 5 - 1000 %IB 1 5 Minimum operate residual current for Phase-
Ground loops
Table 110: ZMCAPDIS (21) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
VBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Disabled
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
OperationPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Phase loops
X1FwPP 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach, Ph-Ph,
forward
R1PP 0.01 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for characteristic
angle, Ph-Ph
RFltFwdPP 0.10 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach, Ph-Ph, forward
Table continues on next page
1MRK505222-UUS C Section 6
Impedance protection
215
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals