Name Type Description
BFI_B BOOLEAN Pickup signal from phase B
PU_C BOOLEAN Pickup signal from phase C
PHPUND BOOLEAN Non-directional pickup, issued from any selected
phase or loop
Table 148: ZMRAPDIS (21) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Group signal for current input
V3P GROUP
SIGNAL
- Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Blocks all output for LOV (or fuse failure) condition
BLKTR BOOLEAN 0 Blocks all trip outputs
PHSEL INTEGER 0 Faulted phase loop selection enable from phase
selector
DIRCND INTEGER 0 External directional condition
Table 149: ZMRAPDIS (21) Output signals
Name
Type Description
TRIP BOOLEAN General Trip, issued from any phase or loop
TR_A BOOLEAN Trip signal from phase A
TR_B BOOLEAN Trip signal from phase B
TR_C BOOLEAN Trip signal from phase C
BFI BOOLEAN General Pickup, issued from any phase or loop
PU_A BOOLEAN Pickup signal from phase A
BFI_B BOOLEAN Pickup signal from phase B
PU_C BOOLEAN Pickup signal from phase C
PHPUND BOOLEAN Non-directional pickup, issued from any selected
phase or loop
Table 150: ZDRDIR (21D) Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- group connection for current abs 2
V3P GROUP
SIGNAL
- group connection for voltage abs 2
Section 6 1MRK505222-UUS C