EasyManua.ls Logo

ABB Relion 670 series - Page 487

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Set value:
Mode
Formula used for complex power calculation
C,A
*
C A
CA
*
S V (I I )= × -
EQUATION2043 V1 EN (Equation 112)
A
*
A
A
S 3 V I= × ×
EQUATION2044 V1 EN (Equation 113)
B
*
B
B
S 3 V I= × ×
EQUATION2045 V1 EN (Equation 114)
C
*
C
C
S 3 V I= × ×
EQUATION2046 V1 EN (Equation 115)
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is
calculated. If this angle is 0° the active power component P is calculated. If this angle
is 90° the reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting Power1(2).
A pickup signal PICKUP1(2) is activated if the calculated power component is larger
than the pick up value. After a set time delay TripDelay1(2) a trip TRIP1(2) signal is
activated if the pickup signal is still active. At activation of any of the two stages a
common signal PICKUP will be activated. At trip from any of the two stages also a
common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) – drop-power1(2)). For
generator reverse power protection the power setting is very low, normally down to
0.02 p.u. of rated generator power. The hysteresis should therefore be set to a smaller
value. The drop-power value of stage1 can be calculated with the Power1(2),
Hysteresis1(2): drop-power1(2) = Power1(2)Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset
after a set time DropDelay1(2). The reset means that the pickup signal will drop out ant
that the timer of the stage will reset.
1MRK505222-UUS C Section 7
Current protection
481
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals