Table 297: Current selection for CVGAPC function
Set value for the
parameter
CurrentInput
Comment
1 PhaseA CVGAPC function will measure the phase A current phasor
2 PhaseB CVGAPC function will measure the phase B current phasor
3 PhaseC CVGAPC function will measure the phase C current phasor
4 PosSeq CVGAPC function will measure internally calculated positive sequence
current phasor
5 NegSeq CVGAPC function will measure internally calculated negative sequence
current phasor
6 3ZeroSeq CVGAPC function will measure internally calculated zero sequence current
phasor multiplied by factor 3
7 MaxPh CVGAPC function will measure current phasor of the phase with maximum
magnitude
8 MinPh CVGAPC function will measure current phasor of the phase with minimum
magnitude
9 UnbalancePh CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the
current phasor of the phase with maximum magnitude and current phasor
of the phase with minimum magnitude. Phase angle will be set to 0° all the
time
10 PhaseA-PhaseB CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase A current phasor and phase B
current phasor (I
A
-I
B
)
11 PhaseB-PhaseC CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase B current phasor and phase C
current phasor (I
B
-I
C
)
12 PhaseC-PhaseA CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase C current phasor and phase L1
current phasor ( I
C
-I
A
)
13 MaxPh-Ph CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
14 MinPh-Ph CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
15 UnbalancePh-Ph CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the ph-
ph current phasor with maximum magnitude and ph-ph current phasor with
minimum magnitude. Phase angle will be set to 0° all the time
The user can select to measure one of the voltage quantities shown in table 298:
Section 10 1MRK505222-UUS C
Multipurpose protection
568
Technical reference manual