Name Values (Range) Unit Step Default Description
PhaseDiffA 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between bus and
line Auto
PhaseDiffM 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between bus and
line Manual
tSCA 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck Auto
tSCM 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck Manual
AutoEnerg Disabled
DLLB
DBLL
Both
- - DBLL Automatic energizing check mode
ManEnerg Disabled
DLLB
DBLL
Both
- - Both Manual energizing check mode
ManEnergDBDL Disabled
Enabled
- - Disabled Manual dead bus, dead line energizing
VLiveBusEnerg 50.0 - 120.0 %VBB 1.0 80.0 Voltage high limit bus for energizing check in
% of UBaseBus
VLiveLineEnerg 50.0 - 120.0 %VBL 1.0 80.0 Voltage high limit line for energizing check in
% of VBaseLine
VDeadBusEnerg 10.0 - 80.0 %VBB 1.0 40.0 Voltage low limit bus for energizing check in
% of VBaseBus
VDeadLineEnerg 10.0 - 80.0 %VBL 1.0 40.0 Voltage low limit line for energizing check in
% of VBaseLine
VMaxEnerg 50.0 - 180.0 %VB 1.0 115.0 Maximum voltage for energizing in % of
VBase, Line and/or Bus
tAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizing check
tManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing check