Name Type Default Description
AU_OPEN BOOLEAN 0 Used for local automation function
AU_CLOSE BOOLEAN 0 Used for local automation function
BL_CMD BOOLEAN 0 Steady signal for block of the command
RES_GRT BOOLEAN 0 Positive acknowledge that all reservations are made
RES_EXT BOOLEAN 0 Reservation is made externally
SY_INPRO BOOLEAN 0 Synchronizing function in progress
SYNC_OK BOOLEAN 0 Closing is permitted by the synchronism-check
EN_OPEN BOOLEAN 0 Enables open operation
EN_CLOSE BOOLEAN 0 Enables close operation
XPOS1 GROUP
SIGNAL
- Group signal from XCBR/XSWI per phase
XPOS2 GROUP
SIGNAL
- Group signal from XCBR/XSWI per phase
XPOS3 GROUP
SIGNAL
- Group signal from XCBR/XSWI per phase
Table 336: SCSWI Output signals
Name
Type Description
EXE_OP BOOLEAN Execute Open command
EXE_CL BOOLEAN Execute Close command
SELECTED BOOLEAN Select conditions are fulfilled
RES_RQ BOOLEAN Request signal to the reservation function
START_SY BOOLEAN Starts the synchronizing function
POSITION INTEGER Position indication
OPENPOS BOOLEAN Open position indication
CLOSEPOS BOOLEAN Closed position indication
POLEDISC BOOLEAN The positions for poles A, B and C are not equal after
a set time
CMD_BLK BOOLEAN Commands are blocked
L_CAUSE INTEGER Latest value of the error indication during command
XOUT BOOLEAN Execution information to XCBR/XSWI
POS_INTR BOOLEAN Stopped in intermediate position
AU_OPEN and AU_CLOSE are used to issue automated commands as
e.g. for load shedding for opening respectively closing to the SCSWI
function. They work without regard to how the operator place selector,
PSTO, is set. In order to have effect on the outputs EXE_OP and