Name Type Default Description
QC2_OP BOOLEAN 0 289G is in open position
QC2_CL BOOLEAN 0 289G is in closed position
QC11_OP BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in open
position
QC11_CL BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in closed
position
QC21_OP BOOLEAN 0 Grounding switch 2189G on busbar WA2 is in open
position
QC21_CL BOOLEAN 0 Grounding switch 2189G on busbar WA2 is in closed
position
QC71_OP BOOLEAN 0 Grounding switch 7189G on busbar WA7 is in open
position
QC71_CL BOOLEAN 0 Grounding switch 7189G on busbar WA7 is in closed
position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1
and WA2
VP_BBTR BOOLEAN 0 Status are valid for apparatuses involved in the busbar
transfer
VP_BC_12 BOOLEAN 0 Status of the bus coupler apparatuses between WA1
and WA2 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing grounding
switches
EXDU_12 BOOLEAN 0 No transm error from any bay connected to WA1/WA2
busbars
EXDU_BC BOOLEAN 0 No transmission error from any other bus coupler bay
QA1O_EX1 BOOLEAN 0 External open condition for apparatus 152
QA1O_EX2 BOOLEAN 0 External open condition for apparatus 152
QA1O_EX3 BOOLEAN 0 External open condition for apparatus 152
QB1_EX1 BOOLEAN 0 External condition for apparatus 189
QB1_EX2 BOOLEAN 0 External condition for apparatus 189
QB1_EX3 BOOLEAN 0 External condition for apparatus 189
QB2_EX1 BOOLEAN 0 External condition for apparatus 289
QB2_EX2 BOOLEAN 0 External condition for apparatus 289
QB2_EX3 BOOLEAN 0 External condition for apparatus 289
QB20_EX1 BOOLEAN 0 External condition for apparatus 2089
QB20_EX2 BOOLEAN 0 External condition for apparatus 2089
QB7_EX1 BOOLEAN 0 External condition for apparatus 789
QB7_EX2 BOOLEAN 0 External condition for apparatus 789
Section 12 1MRK505222-UUS C
Control
710
Technical reference manual