Name Type Default Description
QB61_OP BOOLEAN 0 6189 is in open position
QB61_CL BOOLEAN 0 6189 is in closed position
QC1_OP BOOLEAN 0 189G is in open position
QC1_CL BOOLEAN 0 189G is in closed position
QC2_OP BOOLEAN 0 289G is in open position
QC2_CL BOOLEAN 0 289G is in closed position
QC3_OP BOOLEAN 0 389G is in open position
QC3_CL BOOLEAN 0 389G is in closed position
QC11_OP BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in open
position
QC11_CL BOOLEAN 0 Grounding switch 1189G on busbar WA1 is in closed
position
EXDU_ES BOOLEAN 0 No transm error from bay containing grounding switch
1189G
QB61_EX1 BOOLEAN 0 External condition for apparatus 6189
QB61_EX2 BOOLEAN 0 External condition for apparatus 6189
QB1_EX1 BOOLEAN 0 External condition for apparatus 189
QB1_EX2 BOOLEAN 0 External condition for apparatus 189
Table 370: DB_BUS_A (3) Output signals
Name
Type Description
QA1CLREL BOOLEAN Closing of 152 is allowed
QA1CLITL BOOLEAN Closing of 152 is not allowed
QB61REL BOOLEAN Switching of 6189 is allowed
QB61ITL BOOLEAN Switching of 6189 is not allowed
QB1REL BOOLEAN Switching of 189 is allowed
QB1ITL BOOLEAN Switching of 189 is not allowed
QC1REL BOOLEAN Switching of 189G is allowed
QC1ITL BOOLEAN Switching of 189G is not allowed
QC2REL BOOLEAN Switching of 289G is allowed
QC2ITL BOOLEAN Switching of 289G is not allowed
QB1OPTR BOOLEAN 189 is in open position
QB1CLTR BOOLEAN 189 is in closed position
VPQB1TR BOOLEAN Switch status of 189 is valid (open or closed)
1MRK505222-UUS C Section 12
Control
733
Technical reference manual