position directly (without activating the intermediate positions), either locally or
remotely, using a “select before execute” dialog. One can block the function operation,
by activating the BLOCK input. In this case, the present position will be kept and
further operation will be blocked. The operator place (local or remote) is specified
through the PSTO input. If any operation is allowed the signal INTONE from the
Fixed signal function block can be connected. SLGGIO function block has also an
integer value output, that generates the actual position number. The positions and the
block names are fully settable by the user. These names will appear in the menu, so the
user can see the position names instead of a number.
1MRK505222-UUS C Section 12
Control
755
Technical reference manual