Name Values (Range) Unit Step Default Description
V1Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
V1Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
V1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
V1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
V2Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
V2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
V2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
V2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
V2AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
5% of Ir
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
30% of Ir
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
100% of Ir
Table 563: VMSQI Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
3V0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3V0HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
3V0HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
Table continues on next page
1MRK505222-UUS C Section 15
Monitoring
925
Technical reference manual