EasyManua.ls Logo

ABB Relion 670 series - Page 931

ABB Relion 670 series
1232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
V1Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
V1Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
V1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
V1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
V2Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
V2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
V2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
V2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
V2AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
5% of Ir
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
30% of Ir
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
100% of Ir
Table 563: VMSQI Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
3V0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3V0HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
3V0HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
Table continues on next page
1MRK505222-UUS C Section 15
Monitoring
925
Technical reference manual

Table of Contents

Other manuals for ABB Relion 670 series