Table 610: ETPMMTR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
EALim 0.001 -
10000000000.000
MWh 0.001 1000000.000 Active energy limit
ERLim 0.001 -
10000000000.000
MVArh 0.001 1000.000 Reactive energy limit
DirEnergyAct Forward
Reverse
- - Forward Direction of active energy flow Forward/
Reverse
DirEnergyReac Forward
Reverse
- - Forward Direction of reactive energy flow Forward/
Reverse
EnZeroClamp Disabled
Enabled
- - Enabled Enable of zero point clamping detection
function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive Power
EAFPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for forward active energy
EARPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for reverse active energy
ERFPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for forward reactive energy
ERVPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for reverse reactive energy
1MRK505222-UUS C Section 16
Metering
991