EasyManua.ls Logo

Allen-Bradley Compact GuardLogix 5370 - Page 119

Allen-Bradley Compact GuardLogix 5370
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1769-UM022C-EN-P - June 2018 119
Add, Configure, Monitor, and Replace CIP Safety I/O Devices Chapter 7
7. Click to the right of the safety network number to open the Safety
Network Number dialog box.
8. Click Set.
9.
Verify that the Network Status (NS) status indicator is alternating red/
green
on the correct device before clicking Yes on the confirmation
dialog box to set the SNN and accept the replacement device.
10. Follow your company-prescribed procedures to functionally test the
replaced I/O device and system and to authorize the system for use.

Table of Contents

Related product manuals