EasyManua.ls Logo

ARAG DELTA 80 - Page 23

ARAG DELTA 80
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
SETUP "BASIC SETTINGS"
Par.
7. 4
Conrm access
or data change
Exit the function or
data change
Delete
selected
character
Scroll
(LEFT /
RIGHT)
Data
increase /
decrease
Scroll
(UP /
DOWN)
Enter
selected
character
4A GUIDED SETUP PROCEDURE FOR SELF-PROPELLED MACHINES
- From the "Home" page press F8.
- Select
Self-propelled (Fig. 48) and press OK.
Fig. 48
Start basic settings procedure (Fig. 49)
- Delta 80 guides you through the setup procedure: follow all suggested steps and select required
options.
OK: next step ESC: previous step.
- When message
Press Ok to confirm selected settings,
is displayed, setup is completed. Press OK.
- Now select
Start guidance settings procedure and go to guided setup procedure Fig. 52.
Fig. 49 Fig. 50
OK Next step
ESC Previous step
Fig. 51
BASIC SETTINGS
• IMPLEMENT TYPE
Sprayer (Seletron)
: system with Seletron valves.
Sprayer (Electrovalves): system with electric-activated valves - with gearmotor.
• MAIN VALVE
Main control valve installed on the control unit:
None
2 ways (drain valve)
3 ways (main valve)
• SPRAYING SPOT TYPE
Seletron type: single, twin or fourfold
• FLOWRATE REFERENCE SENSOR
Device used to calculate owrate:
Flowmeter
Pressure sensor: measured pressure is used to calculate application rate.
Both: within the working limits the computer uses the owmeter, otherwise it uses the pressure sensor, ONLY if properly congured.
• TERMINAL NOZZLES
None
"Buffer zone" nozzles
: use switch panel to select nozzle to be used at "Buffer zone", see par. 12.2.1 "Buffer Zone" function enabled on page 74.
• TANK LEVEL SOURCE
Device used to read tank level:
Manual: no device connected
Filling flowmeter
Tank level sensor
CONTINUES

Table of Contents

Other manuals for ARAG DELTA 80

Related product manuals