110-TYPE HARDWARE
The 110A-type terminal block that can be used in the satellite closet is the 110AE1-75FT. It
must be field-terminated to both the white and blue fields.
The 300-pair 110P-type terminal blocks that can be used in the satellite closet are the
110PE1-300CT, 110PE1-300CT/FT, and 110PE1-300FT. The 110PE1-300CT is connectorized
on both the white and blue fields. The 110PE1-300CT/FT is connectorized on the white field
and must be field-terminated on the blue field. The 110PE1-300FT must be field-terminated
on both the white and blue fields.
The 900-pair 110P-type terminal blocks that can be used in the satellite closet are the
110PE1-900CT/FT and the 110PE1-900FT. The 110PE1-900CT/FT is connectorized on the
white field and must be field-terminated on the blue field. The 110PE1-900FT must be
field-terminated on both the white and blue fields.
Station Circuit Distribution From Equipment Room
The following information should be helpful in explaining the station circuit distribution
from the equipment room to the information outlets for new wiring installations. Diagrams
are provided to show the options for running and connecting the station cables.
If most of the voice terminals that require remote powering are within 250 feet (76.2 m) of
the equipment room, 4-pair station circuits are run from the equipment room to the
information outlets. If this is not the case or if the customer requires 2-point
administration, 3-pair station circuits are run to satellite locations. From the satellite
locations, 4-pair station circuits are run to the information outlets.
4-Pair Station Circuits
Four-pair circuits can be run directly from an equipment room cross-connect field to a 258A
or BR2580A adapter as shown in Figure 3-75. Four-pair station cables (DIW) connect the
adapter to the information outlets.
The 4-pair DIW station cables can be run directly from the equipment room to the
information outlets if 4-pair terminal blocks are used in the Distribution Field (see Figure
3-76). The station cables must be field-terminated to the 110 terminal blocks. If modular
plug-ended station cable is to be used, an adapter can be connected directly to the 110
terminal block connectors (see Figure 3-77).
3-100