Installation and Upgrades for DEFINITY ONE and
IP600 Internet Protocol Release 10
555-233-109
Issue 6
December 2001
Install and Cable the Cabinet
1-4Check customer’s order
1
The other Environmental Considerations and System Protection requirements
described in the DEFINITY ECS Systems Description under "Site Requirements"
apply to the Avaya IP600 as well.
Check customer’s order
1. Check the customer’s order and the shipping packing lists to confirm that
all equipment is included.
2. Report missing equipment to an Avaya representative.
3. Check the system adjuncts for damage and report all damage according to
local shipping instructions.
Correct shipping errors
1. Red-tag all defective equipment and over-shipped equipment and return
according to the nearest Material Stocking Location (MSL) instructions.
2. Direct all short-shipped reports to the nearest MSL. Contact the
appropriate location for specific instructions. For streamlined
implementation, call 1-800-772-5409.
Table 1-1. Cabinet Power Source Information
Cabinet Style and Power
Distribution Unit
Power Sources Power Input Receptacles
Rack Mount Cabinet. AC
power supply
(650A integrated
power supply)
There is no integrated DC
power supply. DC rectifiers
can be used if desired; follow
manufacturer’s instructions.
Single phase 120
VAC with neutral
Single phase 240
VAC with neutral
120 VAC, 60 Hz NEMA
5-15R
240 VAC, 50 Hz IEC 320
Japan installations use
country specific
receptacles for 100 and
200 VAC, 50/60 Hz
Table 1-2. Circuit Breakers for AC-Powered Cabinets
Cabinet Type Circuit Breaker Size
Rack Mount Cabinet (120 VAC) 60 Hz 15 A
Rack Mount Cabinet (240 VAC) 50 Hz 10 A