Install and Cable the Cabinet
1-3Site Requirements
1
SECTION I - AVAYA IP600
INSTALLATION
This section covers procedures for installing the IP600 system.
Site Requirements
Avaya IP600 is designed to be mounted in a standard 19-inch (48 cm) data rack
that has been properly pre-installed and secured per local code and the EIA 310
(or equivalent) standards. The customer is responsible for providing the rack and
having it installed and secured prior to Avaya IP600 installation. This also applies
to providing AC power to the rack and approved grounding. The technicians
trained to install the Avaya IP600 do not typically have the tools or proper training
for data rack installation.
If floor mounted (single cabinet only), the technician is responsible for installing
the cabinet per local code.
The Avaya IP600 cabinet dimensions are 12 inches (7U) high by 22 inches deep
by 19 inches wide. The Avaya IP600 cabinet can be mounted at its midpoint by
removing the mounting brackets and remounting them at a medial position.
Installation requires 1 foot (30 cm) of clearance in the rear, and 18 inches (45 cm)
of clearance in the front, which is consistent with the EIA 310 data rack standards.
In a two- or three- cabinet configuration, the dimensions of the TDM/LAN cable
require that one cabinet be mounted directly over the other (flush).
The Avaya IP600 should be installed in a well-ventilated area. Maximum
equipment performance is achieved at an ambient temperature between 40 and
120 degrees F (4 and 49 degrees C) for a short-term operation (not more than 72
consecutive hours or 15 days in a year) and up to 110 degrees F (43 degrees C)
for a continuous operation. The relative humidity range is 10 to 95% at up to 84
degrees F (29 degrees C). Above this, maximum relative humidity decreases from
95% down to 32% at 120 degrees F (49 degrees C). Installations outside these
limits may reduce system life or affect operation. The recommended temperature
and humidity range is 65 degrees to 85 degrees F (18 to 29 degrees C) at 20 to
60% relative humidity.