Install and Cable the Cabinet
1-68Check AC power and ground for DEFINITY ONE
1
Connect cabinet grounds and other grounds
Follow these additional grounding requirements:
■ The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), copper,
stranded wire. This is in addition to the ground wire in the AC power cord.
■ Bond all approved grounds at the single-point ground to form a single
grounding electrode system.
Install the ground block and ground wire on cabinets
1. Mount the ground block as shown in Figure 1-32.
Figure 1-32. Ground block installation to right CMC panel
Figure Notes
1. #12 x 1-inch shoulder screws 2. Single-point ground block
indmingb RPY 012398