Install and Cable the Cabinet
1-24Check AC power and ground for Avaya IP600I
1
Connect cabinet grounds and other grounds
Follow these additional grounding requirements:
The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), copper,
stranded wire. This is in addition to the ground wire in the AC power cord.
Bond all approved grounds at the single-point ground to form a single
grounding electrode system.
4. Connect the cable as shown in Figure 1-10 for an Avaya IP600 single
cabinet, or Figure 1-11 on page 1-25 for two Avaya IP600 cabinets.
Figure 1-10. Single-cabinet RMC grounding
Figure Notes
1. 10 AWG (#25) (6 mm
2
) wire to
coupled bonding conductor
(CBC).
2. 6 AWG (#40) (16 mm
2
) ground wire
from single-point ground block to the
approved building ground.
1
2
cadpgnd1 LJK 102500