Operation using the data setting device Azbil Corporation
5-48 Model MTG11A/18A, MTG11B/18B, MTG14C
5-6-7 : Setting specific gravity
This function is used to set the specific gravity when selecting a weight unit (t, kg, g,
lb) in the flow rate range setting.
Set range: 0.1000 to 5.9999
Default: 1.0000
Set the specific gravity in accordance with the following procedure:
Step Procedure Screen
1 Enter ENGINEERING MODE in accordance with
the entry into ENGINEERING MODE (see
section 5-5-10 : on page 5-36). Then press the
or key to display the screen at right.
2 Press the key to move the cursor to the position
under a desired value to be set or changed.
3 Using the or key, change the value to the
desired one to be set.
4 Press the key to move the cursor to the position
under #.
Press the MODE key to return to the
MEASURING MODE and to save data.
m CAUTION
You have only ten minutes to return to MEASURING MODE to save the new value before
the system resets it to the previously saved value.
12.3 %
# GRAVITY
1.0000
12.3 %
# GRAVITY
1.0000
12.3 %
# GRAVITY
1.0050
12.3 %
# GRAVITY
1.0050
CM2-MTG300-2001.book 48 ページ 2015年9月29日 火曜日 午前10時14分