84 CHA NGE PARA METERS
6.4.7 MOT ORISED PO T RA MP / MP Preset value PIN 53
Note. 50)MP M A X CLA MP and 51)MP MIN CLAMP will overide the output value if it lies outside the clamps.
6.4.8 MOT ORISED PO T RA MP / MP memory boot up PIN 54
A motorised pot is a device that may be used to remember its setting in the event of a power loss.
DISABLED. Used to set the value of the output on control supply po wer up to 53)MP PRESET V ALUE.
ENABLED. Used to memorise the value of the output during loss of the control supply, and preset the
output with this value on po wer up of the control supply.
MO T ORISED PO T RA MP 3
53)MP PRESET V ALUE
53)MP PRESET V ALUE
0.00%
PARA METER RANGE DEFAULT PIN
MP PRESET V ALUE + /-300.00 % 0.00 % 53
The output assumes this value
if MP PRESET is high.
MO T ORISED PO T RA MP 3
54)MP MEMORY BO O T-UP
54)MP MEMORY BO O T-UP
DISABLED
PARA METER RANGE DEFAULT PIN
MP MEMORY BO O T-UP ENABLED or DIS ABLED DIS ABLED 54
Selects the preset output value
on control supply application.